Control of Air Conditioners
A homeowner can control the electric output of their air conditioners with the use of Energy Sentry demand controller. Please note: The following steps should be performed by a licensed electrician and is not recommended for homeowners.
Air conditioning compressors are easiest to control by disconnecting the low-voltage signal from the thermostat to the compressor relay. This is normally the yellow wire (“Y” or “Y1”). Be sure to program a minimum OFF-TIME on the relay of at least 5 minutes to prevent short cycling of the compressor, and a minimum ON-TIME of 6 to 9 minutes for desired comfort level. In most cases, the fan should not be controlled - it should run when the compressor is shed.
Hook-up
- Refer to the A/C schematic and locate the wire from the thermostat that signals the compressor to operate (not the common return line). This can be located in the air handler or at the condensing unit.
- Run a 2-conductor, 18-gauge wire from the control unit to the outdoor unit or the air handler and interrupt the wire located in Step 1 above.
- Program a minimum OFF-TIME on the relay of at least 5 minutes to prevent short cycling of the compressor. Program a minimum ON-TIME of 6 to 9 minutes for desired comfort level.
Previous Tech Tip: Control of Electric Boilers
Next Tech Tip: Control of Air Conditioners/Heat Pumps-Southeast/Southwest